Section R807.1, Attic access, is hereby deleted in its entirety and the following provisions shall be substituted therefor:

Buildings with combustible ceiling or roof construction shall have an attic access opening to attic areas that exceed 30 square feet (2.8 m2) and have a vertical height of 30 inches (762 mm) or greater. The vertical height shall be measured from the top of the ceiling framing members to the underside of the roof framing members.

The rough-framed opening shall not be less than 22 inches by 24 inches (559 mm by 610 mm) and shall be located in a readily accessible location. When located in a wall, the opening shall be a minimum of 22 inches wide by 30 inches high. When the access is located in a ceiling, minimum unobstructed headroom in the attic space shall be 30 inches (762 mm) at some point above the access measured vertically from the bottom of ceiling framing members. See Uniform Mechanical Code for access requirements where mechanical equipment is located in attics.

(Ord. 20467 § 33, 12-5-23.)