Section R903.4.1, Overflow drains and scuppers, is hereby deleted in its entirety and the following provisions shall be substituted therefor:

Where roof drains are required, overflow drains having the same size as the roof drains shall be installed with the inlet flow line located 2 inches (51 mm) above the low point of the roof, or overflow scuppers having three times the size of the roof drains and having a minimum opening height of 4 inches (102 mm) shall be installed in the adjacent parapet walls with the inlet flow located 2 inches (51 mm) above the low point of the roof served. The installation and sizing of overflow drains, leaders and conductors shall comply with the currently adopted edition of the Uniform Plumbing Code.

Overflow drains shall discharge to an approved location and shall not be connected to roof drain lines.