Chapter 6, Section 602.1, General, is hereby deleted in its entirety and the following provisions shall be substituted therefor:

Supply air, return air, and outside air for heating, cooling, or evaporative cooling systems shall be conducted through duct systems constructed of metal as set forth in Tables 6-1, 6-2, 6-3, 6-4, 6-7, 6-8, 6-9, and 6-10, or metal ducts complying with UMC Standard No. 6-2 or the referenced HVAC duct construction standard in Chapter 17. Rectangular ducts in excess of two (2) inches w.g. shall comply with UMC Standard No. 6-2 or the referenced HVAC duct construction standard in Chapter 17. Ducts, plenums, and fittings may be constructed of concrete, clay, galvanized sheet metal coated with corrosion inhibiting material, or ceramics when installed in the ground or in a concrete slab, provided the joints are tightly sealed. PVC ducts encased in a concrete slab may be used only for one and two family residential installations.

Corridors shall not be used to convey air to or from rooms if the corridor is required to be of fire-resistive construction per the Building Code.

Concealed building spaces or independent construction within buildings may be used as ducts or plenums.

When gypsum products are exposed in ducts or plenums, the air temperature shall be restricted to a range from 50°F (10°C) to 125°F (52°C), and moisture content shall be controlled so that the material is not adversely affected. For the purpose of this section, gypsum products shall not be exposed in ducts serving as supply from evaporative coolers, and in other air-handling systems regulated by this chapter when the temperature of the gypsum product will be below the dew point temperature.

See Chapter 8 for limitations on combustion products venting systems extending into or through ducts and plenums.

See Chapter 5 for limitations on environmental air systems exhaust ducts extending into or through ducts or plenums.

Exhaust ducts under positive pressure and venting systems shall not extend into or pass through ducts or plenums. For appliance vents and chimneys, see Chapter 8.

(Ord. 19216 § 18, 2-3-09. Code 1995 § 26-504.)